Abstract:
This paper implements an undervoltage protection function for distributed generators connected to distribution systems, which complies with the recent low-voltage-ride-th...Show MoreMetadata
Abstract:
This paper implements an undervoltage protection function for distributed generators connected to distribution systems, which complies with the recent low-voltage-ride-through requirements. This function takes account of the adopted low-voltage-ride-through curve, as well as the relevant requirements concerning consecutive low-voltage disturbances. In this regard, it can preserve low-voltage-ride through operation, concurrently preventing an excessive network energization by the generator. The designed function is described in detail, while, it is modelled using MATLAB/Simulink. Furthermore, it is tested by simulating different kinds of consecutive low-voltage disturbance events.
Date of Conference: 09-12 March 2020
Date Added to IEEE Xplore: 09 June 2021
Print ISBN:978-1-83953-277-1