Abstract:

A methodology for sectionalizer control has been developed that provides more security for applications where system transient currents may cause actuate pick-up. Actuate...Show More

Abstract:

A methodology for sectionalizer control has been developed that provides more security for applications where system transient currents may cause actuate pick-up. Actuate pick-up particularly on ground sensing, may occur during upline ground faults when the sudden load current imbalance is compounded by the unfaulted phase voltage rise causing magnetizing current inrush into a large amount of distribution transformers downline from the sectionalizer. Motor backfeed and nonsimultaneous fault clearing may cause actuate pickup if the load is sufficiently large. The control has five automatic restraint features: inrush restraint, count restraint, time-integrated threshold restraint, response restraint, and ground restraint. The last three are new features. The control logic was tested by connecting a prototype to the transient network analyze and simulating conditions that were suspected of causing problems.<>
Published in: IEEE Transactions on Power Delivery ( Volume: 7, Issue: 2, April 1992)
Page(s): 876 - 882
Date of Publication: 30 April 1992