Introduction
Two-level three-phase voltage-source inverters (VSI) is widely used in various kinds of applications, including photovoltaic inverter, electric vehicle, energy storage system, etc. Even though the efficiency of some commercial inverters is pretty high, their power density has not been improved significantly due to the relatively low switching frequency of silicon IGBTs. The silicon carbide (SiC) MOSFETs have faster switching speeds and lower switching loss compared with their Si counterparts [1]. Nevertheless, the total switching loss still increases sharply when operating at hundreds of kilohertz. Since the turn-on loss of the SiC MOSFET is much higher than the turn-off loss, the zero-voltage-switching (ZVS) technique can be used to eliminate the turn-on loss and improve the efficiency even operating at high frequency [2].
Various kinds of soft-switching methods have been proposed and conducted over the recent years [3], [4], [5], [6], [7], [8]. Most of them need auxiliary circuits to produce high current ripple to realize the ZVS of power devices. They can be divided into resonant DC link (RDCL) inverters [3], [4], [5] and auxiliary resonant commutated pole (ARCP) inverters [6], [7], [8] based on the position of the auxiliary circuits. These methods can realize soft switching of the main switches and the auxiliary switches at a fixed switching frequency, but the costs and complexity are greatly increased.
A simple way to achieve ZVS without additional circuits is to increase the inductor current ripple and change its direction in each switching cycle. The output capacitor of the power device can then be charged and discharged during the dead time. This idea known as critical conduction mode (CRM) or triangular current mode (TCM) has been successfully implemented to realize the ZVS of buck/boost converter [9], totem-pole bridgeless power factor correction (PFC) rectifier [10], and three-phase inverter [11], [12], [13]. Zero current detection (ZCD) circuit and high frequency current sensor is needed to determine the switching instant. However, the switching frequency variation range is quite large in a line cycle. In [14], discontinuous pulse width modulation (DPWM) and frequency synchronization concept is adopted to reduce the frequency range. The switching state of one phase-leg is fixed, and the other two phase-legs switch at high frequency. To synchronize the switching frequency of the two phase-legs, the former phase-leg runs in discontinuous conduction mode (DCM), and the latter phase-leg works in CRM. Zero-current switching (ZCS) instead of ZVS is achieved for some switches.
A current ripple prediction (CRP) and DPWM-based fully digital control ZVS technique is proposed in [15]. No additional sensor or auxiliary circuit is needed. The variable switching frequency can be simply calculated based on the sampled voltage and current information. This method has also been used in two parallel interleaved three-phase inverters to achieve higher power level [16]. The high current ripple can be cancelled by the interleaving structure so the filter size is further reduced. According to the operating principle of these methods, lower current ripple is required at light load, so the switching frequency increases sharply as power decreases. Although the turn-on loss is eliminated, the turn-off loss is significantly increased at light load due to the high frequency.
A phase-shedding control method is used in multi-phase dc-dc converters [17], [18] and PFC circuits to improve the light load efficiency [19], [20]. The main idea is to reduce the number of operating phase-legs at a light load. Then the switching frequency will decrease, and the switching loss and the driving loss will also drop. In [21], a CRM-based phase shedding control for two-channel parallel three-phase inverter is proposed. The switching frequency is decreased with only four phase-legs operation. However, dynamic current sharing between the two clamping phase-legs is not achieved, and circulating current exists. Meanwhile, ZCD circuits and high frequency current sensors are still indispensable.
In this paper, the phase shedding control is applied to the CRP based two parallel interleaved three-phase inverters. A new variable switching frequency control method is proposed with only four operating phase-legs. To further improve the light load efficiency, a current-sharing method is proposed, and the circulating current is eliminated. Compared with the six phase-legs operation, the switching frequency is greatly reduced with only four phase-legs under the same light load. The switching loss is further decreased, so the light load efficiency is improved. The modulation scheme and the current ripple control method are analyzed in Section II. The switching frequency calculation is discussed in Section II-B. The simulation and experimental verification are illustrated in Section III. Finally, Section IV gives the conclusion.
Space Vector Modulation Methods and Inductor Current Ripple Analysis
Fig. 1 shows the configuration of the two parallel interleaved three-phase inverters. The six inverter-side inductors
A. Analyses of Circulating Current and Four Phase-Legs Operation
Under heavy load conditions, DPWM method is used so that at any time only two phases (four phase-legs) are switching. The other phase (two phase-legs) is in clamping mode whose switching state remains constant in a sector. In this way, not only the ZVS realization condition is weakened from 12 switches to 8 switches, but the three-phase currents are also decoupled [16]. To reduce the unnecessary current ripple at light load, the switching frequency increases with the decrease of the phase current. For the parallel interleaving structure, two inverters share the grid current, so the switching frequency is quite high at light load. The turn-off loss increases significantly despite the elimination of the turn-on loss.
To improve the light load efficiency, the phase-shedding technique can be used. The second inverter stops switching (three phase-legs shedding), so the entire power is processed by the first one. However, undesired circulating currents appear between the two clamping phase-legs. The simulation waveforms are illustrated in Fig. 2.
Since there is no switching loss during the clamping state, when the phase-leg of inverter 1 is in the clamping state, the corresponding phase-leg of inverter 2 can also be clamped in the same state. In this way (two phase-legs shedding), not only the circulating current is eliminated, but two clamping phase-legs can also share the phase current and further reduce the conduction loss. Fig. 4 shows the switching patterns of inverter 2 in a line cycle. Each of the six switches is turned on for 60° consecutively.
B. Current Ripple Analysis Under Four Phase-Legs Operation
Sector 1 is taken as an example to show the operating principle with four phase-legs. As shown in Fig. 5 (a), from \begin{align*} \begin{cases} \displaystyle i_{x1} \left ({{t_{0}} }\right)=i_{gx}, i_{x1} \left ({{t_{0} -\Delta t} }\right)+i_{x1} \left ({{t_{0} +\Delta t} }\right)=2i_{gx} \\ \displaystyle i_{x1} \left ({{t_{3}} }\right)=i_{gx}, \textrm {}i_{x1} \left ({{t_{3} -\Delta t} }\right)+i_{x1} \left ({{t_{3} +\Delta t} }\right)=2i_{gx} \end{cases} \tag{1}\end{align*}
The requirements to achieve ZVS for phase \begin{equation*} i_{x1} \left ({{t_{on}} }\right) < -I_{bias}, i_{x1} \left ({{t_{off}} }\right) > I_{bias} \tag{2}\end{equation*}
According to (1), equation (2) can be rewritten as \begin{equation*} i_{x1} \left ({{t_{off}} }\right)-i_{x1} \left ({{t_{on}} }\right) > 2I_{bias} +2\left |{ {i_{gx}} }\right | \tag{3}\end{equation*}
In Fig. 5 (a), the current ripple of
Equivalent circuits for current ripple calculation during
Based on Thevenin’s theorem, from \begin{equation*} L_{1} {\Delta i_{c1}} \mathord {\left /{ {\vphantom {{\Delta i_{c1}} {\Delta t}}} }\right. } {\Delta t}={v_{a}} \mathord {\left /{ {\vphantom {{v_{a}} 4}} }\right. } 4-v_{c} \tag{4}\end{equation*}
From \begin{equation*} L_{1} {\Delta i_{b1}} \mathord {\left /{ {\vphantom {{\Delta i_{b1}} {\Delta t}}} }\right. } {\Delta t}=(V_{dc} +v_{a})/4-v_{b} \tag{5}\end{equation*}
The time duration of each mode can be expressed by the modulation wave \begin{align*} \begin{cases} \displaystyle t_{5} -t_{1} ={m_{b}} \mathord {\left /{ {\vphantom {{m_{b}} {f_{s}}}} }\right. } {f_{s}} \\ \displaystyle t_{4} -t_{2} ={\left ({{1-m_{c}} }\right)} \mathord {\left /{ {\vphantom {{\left ({{1-m_{c}} }\right)} {f_{s}}}} }\right. } {f_{s}} \end{cases} \tag{6}\end{align*}
Thus, equation (5) can be rewritten as \begin{align*} \begin{cases} \displaystyle f_{sb} < \frac {m_{b} (2V_{dc} -v_{a} +4v_{b})}{8L_{1} \left ({{\left |{ {i_{b1}} }\right |+I_{bias}} }\right)} \\ \displaystyle f_{sc} < \frac {\left ({{1-m_{c}} }\right)\left ({{v_{a} -4v_{c}} }\right)}{8L_{1} \left ({{\left |{ {i_{c1}} }\right |+I_{bias}} }\right)} \end{cases} \tag{7}\end{align*}
It means switches
Similarly, during \begin{align*} \begin{cases} \displaystyle f_{sa} < \frac {m_{a} \left ({{4v_{a} -v_{c}} }\right)}{8L_{1} \left ({{\left |{ {i_{a1}} }\right |+I_{bias}} }\right)} \\[8pt] \displaystyle f_{sb} < \frac {(1-m_{b})(2V_{dc} -4v_{b} +v_{c})}{8L_{1} \left ({{\left |{ {i_{b1}} }\right |+I_{bias}} }\right)} \end{cases} \tag{8}\end{align*}
C. Switching Instant Synchronization of the Fourth Phase-Leg
In this part, the turn-on instant of the fourth phase-leg is discussed. In a digital controller, the compare value in a PWM module is generally updated at the peak or the valley of the carrier wave. Therefore, after the change of the clamping state, a straightforward way to turn on the fourth phase-leg is also at the peak or the valley. Take phase
To avoid the circulation current and achieve dynamic current sharing,
Switching Frequency Selection and Comparison
The critical switching frequencies in sector 1 with four operating phase-legs are derived in (7) and (8). To achieve ZVS for all the switches and minimize the unnecessary current ripple, the lower critical frequency should be chosen as the inverter unified switching frequency. Assuming the circuit parameters are listed in Table 1, the critical switching frequencies for both phases to achieve ZVS at different loads in sector 1 are shown in Fig. 9. The dashed lines are
Critical switching frequencies for each phase with DPWM at different loads in sector 1.
For other sectors, the three-phase voltages and currents simply exchange their positions, so the current ripple analyses and critical frequency calculations are the same. The derivation of the equations in other sectors is omitted. The general frequency calculation equation operating with four phase-legs is concluded as \begin{equation*} f_{sy} < \frac {\left ({{1-m_{y}} }\right)\left ({{v_{x} -4v_{y}} }\right)}{8L_{1} \left ({{\left |{ {i_{y1}} }\right |+I_{bias}} }\right)}, f_{sz} < \frac {m_{z} \left ({{4v_{z} -v_{x}} }\right)}{8L_{1} \left ({{\left |{ {i_{z1}} }\right |+I_{bias}} }\right)} \tag{9}\end{equation*}
Fig. 10 shows the switching frequency variation with six phase-legs operation and four phase-legs operation at different loads in a line cycle. It can be seen that if two inverters keep operating under light load lower than 2500 W, the switching frequency will increase to above 300 kHz. Frequency limitation is necessary to avoid high turn-off loss at lighter load. However, with the proposed four phase-legs operation mode, the switching frequency at light load significantly reduces. Therefore, the frequency variation range of the whole load condition is narrower than the conventional operation.
Critical switching of the four phase-legs and six phase-legs operation at different loads.
The whole control method can be easily implemented in a digital controller without using any additional auxiliary circuits or sensors. The control block diagram is shown in Fig. 11. The driving signals of each phase-leg in inverter 1 are always complementary based on the DPWM modulation. The only difference of inverter 1 between six and four phase-leg modes is the calculation of the switching frequency. Inverter 2 also works in DPWM mode with 180° phase delay of the carrier wave in six phase-leg mode. However, in four phase-leg mode, the driving signal of inverter 2 is generated directly based on the clamping state. The selection criteria between the two modes is based on the output power calculated by the grid voltage and current. When the power is lower than the preset value, four phase-leg mode is used instead of six phase-leg. The specific power of the mode change can be determined by the efficiency curves shown in the experiment section. In this paper, 50% power is set as the changing point.
Simulation and Experiment Verification
To verify the effectiveness of the control strategy, the simulation and experiment waveforms are illustrated in this section. The specifications and parameters of the inverter are given in Table 1. Fig. 12 shows the simulation waveform at half load in a line cycle. In sector 1, the upper envelop lines of
The high-frequency current ripples in the inverter side flow through the filter capacitors and are filtered out, so the grid currents have very low distortion even with small filter parameters. The switching frequency variation is the same for all the sectors, and the frequency is continuous and smooth in a line cycle.
Fig. 13 shows
Fig. 14 shows the photograph of the experimental prototype. It is fabricated using twelve SiC MOSFETs (C3M0060065K, 650 V, 60
To verify the effectiveness of the proposed method at light load, the experiment is conducted at 50% load. The steady-state experimental waveform of phase
The ZVS waveforms of the top switch
For the bottom switch
Fig. 18 shows the inductor currents and the driving signals of the two phase-legs of phase
Fig. 19 shows the dynamic response of the inverter during the load step change from 60% to 20%. It can be seen that
The power loss of the inverter is mainly composed of the conduction loss and turn-off loss of the switches, the core loss, and copper loss of the inductors. The capacitors’ losses are so small that can be omitted. The comparison of the inverter loss breakdown between the four and six phase-legs operation at 50% load is given in Fig. 20. With the proposed phase-shedding control method, the conduction loss and the copper loss of
Conclusion
In this paper, a phase-shedding control is proposed for CRP based two parallel interleaved three-phase ZVS inverters to improve the light load efficiency. DPWM and variable switching frequency are used to achieve ZVS for all the switches. The critical switching frequency can be easily calculated in a digital controller based on current ripple prediction. Compared with the previous six phase-legs operation, the switching frequency under four phase-legs operation is greatly decreased. The turn-off loss is minimized and the frequency variation range is much narrower. Inductor current sharing can be achieved between the two inverters during the clamping mode, so the circulating current is eliminated. Owing to the high switching frequency and the low inductance, the size and the cost of the inverter can be greatly reduced. Fast dynamic response is realized and ZVS can also be achieved during transients. With the proposed control strategy, higher efficiency is achieved for the two parallel interleaved inverters at light load.