Abstract:
Performance testing of a ground fault protection system has traditionally been accomplished by simulating high level fault magnitudes at current transformer secondary. Fo...Show MoreMetadata
Abstract:
Performance testing of a ground fault protection system has traditionally been accomplished by simulating high level fault magnitudes at current transformer secondary. For a new chemical manufacturing facility, a procedure was devised to safely stage ground faults on the 480 volt distribution system. To implement the procedure, a test set was developed that placed a controlled ground fault on the system and measured current magnitude and tripping time. Tests were conducted without the need to modify the distribution system or the ground protection wiring in any way. This feature revealed discrepancies that would not have been discovered following more conventional test methods.
Published in: 1983 Annual Meeting Industry Applications Society
Date of Conference: 03-07 October 1983
Date Added to IEEE Xplore: 16 May 2023
Print ISBN:978-1-5090-3188-7
Print ISSN: 2576-702X
Conference Location: Mexico City, Mexico