Abstract:

In this paper, we propose a new time-frequency based analysis method that monitors the state of the high temperature superconducting (HTS) cable system in a real-time man...Show More

Abstract:

In this paper, we propose a new time-frequency based analysis method that monitors the state of the high temperature superconducting (HTS) cable system in a real-time manner and detects the current imbalance of HTS cable system. The new time-frequency-based method utilizes the cross Wigner-Ville distribution to analyze the time-frequency localized phase difference of the reflected signal, which varies depending on the insulation characteristics of the HTS cable system. Also, a real-world AC 22.9 kV 50 MVA HTS cable system and a current source are used to validate the performance of the new monitoring method in order to detect current imbalance phenomenon.
Published in: IEEE Transactions on Applied Superconductivity ( Volume: 28, Issue: 4, June 2018)
Article Sequence Number: 2500205
Date of Publication: 26 February 2018