Two-Terminal Traveling-Wave-Based Transmission-Line Protection | IEEE Journals & Magazine | IEEE Xplore

Two-Terminal Traveling-Wave-Based Transmission-Line Protection


Abstract:

This paper proposes a two-terminal traveling-wave-based transmission-line protection using only the first wavefront arrival time at each line terminal (polarity and magni...Show More

Abstract:

This paper proposes a two-terminal traveling-wave-based transmission-line protection using only the first wavefront arrival time at each line terminal (polarity and magnitude of transients are not required), leading to a simple, accurate, and fast protection. In real time, the protection system detects internal and external faults and identifies the fault directionality. In addition, the protection zone and the protection operating time are also formulated. The effects of the sampling rate and the traveling-wave propagation velocity estimation are considered, and some paradigms, such as the need of a high-sampling frequency and an accurate traveling-wave propagation velocity estimation are properly addressed. Two traveling-wave-based protective relays were implemented and evaluated in realistic real-time hardware-in-the-loop simulations considering the communication equipment between the relays, in which reliability and protection operating time could be assessed accordingly.
Published in: IEEE Transactions on Power Delivery ( Volume: 32, Issue: 3, June 2017)
Page(s): 1382 - 1393
Date of Publication: 01 June 2016

ISSN Information:

Funding Agency:


Contact IEEE to Subscribe

References