Dielectric Tests for EHV Transformers | IEEE Journals & Magazine | IEEE Xplore

Dielectric Tests for EHV Transformers


Abstract:

Specific proposals for revision of dielectric tests for EHV power transformers are made. An objective is improved operating reliability by specifying tests which are more...Show More

Abstract:

Specific proposals for revision of dielectric tests for EHV power transformers are made. An objective is improved operating reliability by specifying tests which are more compatible with service requirements. Impulse and switching surge tests are coordinated independently with lightning arrester characteristics. Low-frequency tests are disassociated from transient voltage requirements and are related to operating voltage only. Low-frequency test voltages are reduced and their duration is increased; absence of corona during the test is required. Suggestions for further development work are made.
Published in: IEEE Transactions on Power Apparatus and Systems ( Volume: PAS-87, Issue: 1, January 1968)
Page(s): 135 - 145
Date of Publication: 29 January 2007
Print ISSN: 0018-9510

Contact IEEE to Subscribe

References