  • Numerical simulation of partial discharge propagation in cable joints using the finite difference time domain method

    Publication Year: 2002, Page(s):6 - 11
    Cited by:  Papers (14)
    Request permission for commercial reuse | Click to expandAbstract | PDF file iconPDF (6578 KB) | HTML iconHTML

    In this second of a series of three papers, the authors investigate partial discharge (PD) detection and propagation in cable joints. The complex nature of cable joints leads to errors when PD analysis is carried out using conventional equivalent circuits. The authors use the finite difference time domain method to determine the transient electromagnetic fields caused by simulated PD in model cabl... View full abstract»

    Full text access may be available. Click article title to sign in or learn about subscription options.
  • Review of condition assessment of power transformers in service

    Publication Year: 2002, Page(s):12 - 25
    Cited by:  Papers (277)
    Request permission for commercial reuse | Click to expandAbstract | PDF file iconPDF (1296 KB) | HTML iconHTML

    As transformers age, their internal condition degrades, which increases the risk of failure. To prevent these failures and to maintain transformers in good operating condition is a very important issue for utilities. Traditionally, routine preventative maintenance programs combined with regular testing were used. The change to condition-based maintenance has resulted in the reduction, or even elim... View full abstract»

    Full text access may be available. Click article title to sign in or learn about subscription options.
  • Effective diagnostics for oil-filled equipment

    Publication Year: 2002, Page(s):26 - 38
    Cited by:  Papers (47)  |  Patents (2)
    Request permission for commercial reuse | Click to expandAbstract | PDF file iconPDF (646 KB) | HTML iconHTML

    The author describes an approach used in Russia to develop diagnostic techniques to assess the condition of oil-filled power equipment. He considers that the most useful parameters to estimate remaining life are the partial pressures of dissolved gases and water in the oil and the water content in the solid insulation. Gas chromatography is used to determine these parameters from oil samples taken... View full abstract»

    Full text access may be available. Click article title to sign in or learn about subscription options.
  • Author Index

    Publication Year: 2002, Page(s):53 - 54
    Request permission for commercial reuse | PDF file iconPDF (201 KB)
    Freely Available from IEEE
  • Subject index

    Publication Year: 2002, Page(s):55 - 64
    Request permission for commercial reuse | PDF file iconPDF (459 KB)