The impact of inrush currents on the mechanical stress of high voltage power transformer coils

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

2 Author(s)
Steurer, M. ; High Voltage Lab, Swiss Fed. Inst. of Technol., Zurich, Switzerland ; Frohlich, K.

From failure experience on power transformers, it was very often suspected that inrush currents, occurring when energizing unloaded transformers, were reason for damage. In this paper, it was investigated how mechanical forces within the transformer coils build up under inrush compared to those occurring at short circuit. Two-dimensional and three-dimensional computer modeling for a real 268 MVA, 525/17.75 kV three-legged step up transformer was employed. The results show that inrush current peaks of 70% of the rated short circuit current cause local forces in the same order of magnitude as those at short circuit. The resulting force summed up over the high voltage coil is even three times higher. Although inrush currents normally are smaller, the forces can have similar amplitudes as those at short circuit however with longer exposure time. Therefore, care has to be taken to avoid such high inrush currents. Today controlled switching offers an elegant and practical solution

Published in:

Power Delivery, IEEE Transactions on  (Volume:17 ,  Issue: 1 )