Thevenin source resistances of the touch, transferred and step voltages of a grounding system

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $31
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

3 Author(s)
Chow, Y.L. ; Waterloo Univ., Ont., Canada ; Salama, M.M.A. ; Djogo, G.

The source resistances for surface voltages (touch, transferred and step voltage) are considered. It is proved that the source resistances of the touch and transferred voltages are the same, given by the grounding resistances between the feet of a human and the grounding system. In a practical situation, however, this resistance is very close to that of the ANSI/IEEE Standard 80 that is widely accepted. The source resistance of the step voltage is simply the resistance between the two feet, not at all perturbed by the grounding system. Proofs are derived rigorously by combining the field Galerkin's moment method and basic circuit theory

Published in:

Generation, Transmission and Distribution, IEE Proceedings-  (Volume:146 ,  Issue: 2 )