Adaptability of PSS while the connection between Northeast and North Grids of China changed from AC to DC

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Gao Lei ; CEPRI, Beijing, China ; Zhu Fang ; Zhao Hongguang ; Liu, C.Q.

In this study, the influence of either AC or DC interconnection on the dominant oscillation mode and the frequency response of generator were conducted. Also conducted was the adaptability of PSSs to AC or DC connection of the North East China Grid (NECG) and the North China Grid (NCG). Both complex frequency domain and time domain methods were employed. For analyzing small disturbance stability, not only the dominant area modes but also the local modes were studied in detail. . Based on the above studies, Power System Stabilizer (PSS) adaptability to different connections of the two power grids was demonstrated. The results demonstrate that the present PSS setting of NECG for AC connection with NCG can meet the normal operating requirements for the DC connection.