Direct calculation of the stability domains of three-phase ferroresonance in isolated neutral networks with grounded neutral voltage transformers

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
4 Author(s)

Stability domains of ferroresonant oscillations must be computed and, if needed, countermeasures must be taken in order to avoid serious damage to the power networks' equipment. In this paper, Clarke components are used to write the equations of a representative three-phase circuit under a canonical form and give a simple physical interpretation of the three-phase ferroresonance phenomenon. A method is proposed to approximate the quasi-periodic oscillations by periodic ones. The solutions and their domains of stability are computed by the harmonic balance method. An application to a field case is presented

Published in:

Power Delivery, IEEE Transactions on  (Volume:11 ,  Issue: 3 )