Scheduled System Maintenance:
Some services will be unavailable Sunday, March 29th through Monday, March 30th. We apologize for the inconvenience.
By Topic

Low voltage ride-through analysis of 2 MW DFIG wind turbine - grid code compliance validations

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
4 Author(s)

The transient behavior of the 2 MW wind turbine under a symmetrical 3-phase voltage dip with zero remaining voltage and unsymmetrical phase-to-phase disturbance with 20 % residual voltage is experimentally studied. The results of the voltage dip tests are compared with simulation study. The comparison of the results shows close agreement; therefore validated simulation model is suitable for performing wind turbine voltage dip test simulations without a need to make the site tests. The developed model is also suitable for accurate transient simulation of the small wind park with reduced number of wind turbines. Additionally it can be used as a reference model for the optimization and verification of the simplified turbine model used in power system analysis software.

Published in:

Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE

Date of Conference:

20-24 July 2008