Ground Fault Protection for Bus-Connected Generators in an Interconnected 13.8-kV System

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$33 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

1 Author(s)
J. C. Das ; AMEC E&C Services, Inc, Tucker, GA

This paper is based on modifications implemented in the protection and grounding systems of a large paper mill and describes selective ground fault protection for a 13.8-kV system with multiple bus-connected generators, synchronous bus ties, and utility interconnections. The ground fault current in the system is reduced from the existing 3400 A to 500 A, and a hybrid grounding system is implemented for each of the generators. As the ground fault currents are reduced to limit the fault damage, the sensitivity and selectivity of the ground fault protection become important. Directional ground fault relays with coordinating pickup settings are applied to achieve this objective. The new platform for directional elements (numerical relays) drives its performance from sequence impedance measurements