Multi-break arc interaction in the energy balance region

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

2 Author(s)
Smith, T.M. ; Dept. of Electr. Eng., Pittsburgh Univ., PA, USA ; Colclaser, R.G.

It is postulated that the performance of a multi-break interrupter can be better than that expected from an extrapolation of the test results on a single-break unit. A computer model was developed to study the interaction processes in the energy balance region under short line fault conditions, using a Mayr model differential equation to model arc behavior. This nonlinear equation and the equations representing the electrical network and fault condition were solved for variations in selected parameters and expected unbalances in the voltage distribution across the interrupter units. Comparisons were made between the simulation of a circuit breaker with two interrupting breaks and one with a single break and an equivalent voltage stress. In the neighborhood of criticality, the two-break configuration interrupted the fault current, whereas the single break failed. It was shown experimentally that for equivalent voltage stresses, a two-break interrupter reached the dielectric reignition phase, while the single-break reignited thermally. This supports a concept of sharing between breaks

Published in:

Power Delivery, IEEE Transactions on  (Volume:3 ,  Issue: 4 )