Analysis of Operating Conditions of Ground-Fault Protection Schemes for Generator Stator Winding

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
2 Author(s)
M. Zielichowski ; Wroclaw University of Technology; ABB Corporate Research ; M. Fulczyk

This paper presents results of simulation studies of the influence of methods of grounding the stator winding of the unit-connected generator neutral on the operating conditions of a 100% ground-fault protection excited by the third harmonic voltages ratio in the generator neutral and at its terminals. The analysis was performed for a generator with the neutral grounded through a ground-fault neutralizer, a third harmonic stop filter, a resistor, and a capacitive voltage divider. The influence of the parameters of the particular elements of the grounding circuits on the voltage feeding measuring element of the protection was determined. The capacitance to ground of the generator breakers was taken into account. The simulations were run for 1,110 MVA unit-concerted generator at ground faults along the whole length of the generator stator winding. It has been found that the method of grounding the generator neutral and the parameter of the grounding elements significantly influences the operating conditions of this protection. It is shown that, through the proper selection of these parameters, the ground-fault protection of whole stator winding, counting from the generator neutral to the terminals, is ensured.

Published in:

IEEE Power Engineering Review  (Volume:22 ,  Issue: 12 )