Earth fault distance computation with artificial neural network trained by neutral voltage transients

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
2 Author(s)
Hanninen, S. ; Energy Syst., VTT Energy, Espoo, Finland ; Lehtonen, M.

A novel application of the neural network approach for transient based earth fault location in 20 kV radial power distribution networks is presented. The items discussed are earth fault transients, signal pre-processing, ANN training and the performance of the proposed distance estimation method. The distribution networks considered are either unearthed or resonant earthed. Neural networks trained by the harmonic content of neutral voltage transients were found to be applicable to fault distance computation in the case of very low fault resistance. The mean error in fault location was about 1 km in the field tests using staged faults, which were recorded in real power systems

Published in:

Power Engineering Society Summer Meeting, 2001  (Volume:2 )

Date of Conference:

2001