Induced voltages and currents on gas pipelines with imperfect coatings due to faults in a nearby transmission line

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
3 Author(s)
Christoforidis, G.C. ; Dept. of Electr. & Comput. Eng., Aristotle Univ. of Thessaloniki, Greece ; Dokopoulos, P.S. ; Psannis, K.E.

An improved hybrid method is discussed, employing a finite-element method along with Faraday's law and standard circuit analysis, in order to predict the induced voltages and currents on a pipeline with defects on its coating, running parallel to a faulted line and remote earth. Such defects are a frequent situation especially when old pipelines are considered and are modeled as resistances, called leakage resistances. The fault is assumed to be outside the parallel exposure so that conductive interference is negligible and therefore the problem is a two-dimensional one. Input data are power line and pipeline configuration, physical characteristics of conductors and pipeline, fault and power system terminal parameters and location and value of leakage resistances. Simulation results show that for small values of leakage resistances, defects act as a mitigation method for the induced voltages on the pipeline. However, in that case large currents that flow to earth through the defects can damage the pipeline

Published in:

Power Tech Proceedings, 2001 IEEE Porto  (Volume:4 )

Date of Conference:

2001