Study on recovery time of a superconducting fault current limiter with adjustable trigger current level

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

7 Author(s)
Shirai, Y. ; Dept. of Eng. Sci. & Technol., Kyoto Univ., Japan ; Fujikawa, K. ; Kitagawa, T. ; Shiotsu, M.
more authors

The recovery time of a transformer type SCFCL (superconducting fault current limiter) with adjustable trigger current level, is studied experimentally The recovery time is defined as the required time of zero current period of SCFCL for recovery from its current limiting mode to its waiting mode. A trial SCFCL, which was designed and made, is tested to measure the recovery time with various fault time. The experimental results show that the recovery time depends on the fault time. When the fault time is longer than 200 ms, the recovery time becomes shorter and approaches a certain value (a few ten ms) as the fault time is longer