Temperature rise distribution at the drawlead cables in the condenser bushings was studied with a thermal model and actual thermal tests. Temperature rise of the hottest spot at the cables from the model is consistent with that from the tests within a 10% deviation. Factors that influence working current and overload capacity of the cable were studied. Current-carrying capacities of the drawlead cables with index 105 insulation are presented based on thermal basis of rating
Published in:
Power Delivery, IEEE Transactions on
(Volume:15
,
Issue:
3
)
Date of Publication: Jul 2000