Electroluminescence technique to evaluate the effect of impulse tests on high voltage cables

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

3 Author(s)
Bamji, S.S. ; Nat. Res. Council of Canada, Ottawa, Ont., Canada ; Kaufhold, M. ; Bulinski, A.T.

EL (electroluminescence) in XLPE (crosslinked polyethylene) subjected to impulses of various amplitudes, shapes and repetition rates has been investigated. Defects that could occur in the polymeric insulation of underground HV cables were simulated by embedding semicon protrusions in XLPE to create highly divergent electric fields. Time resolved measurement of the EL pulses emitted during positive, negative or alternating polarity impulses has shown that the EL pulses are grouped into two distinct time periods between which there is no EL activity. The EL emission probability increased with fall time of the impulse voltage but was independent of the impulse rise time. A study of electroluminescence characteristics from unaged and aged XLPE, subjected to a pair of positive and negative impulses, indicated that the charge trapped in the polymeric insulation during aging plays an important role during impulse application and could affect insulation failure

Published in:

Dielectrics and Electrical Insulation, IEEE Transactions on  (Volume:5 ,  Issue: 2 )