Neutral impedances in fault analysis

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$33 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

1 Author(s)
Enns, Mark K. ; Electrocon Int. Inc., Ann Arbor, MI, USA

Object-oriented modeling of transformers and other Y-connected devices preserves neutral nodes and impedances, making them available as points to fault. This is in contrast to conventional modeling in which all neutral nodes are eliminated by modifying the parameters of the devices. Phase-domain expressions are developed for faults between an energized node and a neutral node, and between two neutral nodes. An example using a three-circuit transformer shows the effects of faulting various neutral points. The results show that fault currents may be either higher or lower than for standard phase-to-ground faults, depending on the interaction of source, transformer, and neutral device impedances. The modeling was verified by comparison with phase-to-ground faults on a conventional transformer model

Published in:

Power Systems, IEEE Transactions on  (Volume:13 ,  Issue: 2 )