High-voltage power metering systems based on electronic instrument transformers (EITs) have some advantages compared to the conventional ones. This paper describes an unique calibration method and device for the power metering system. High accuracy with the calibration method can be achieved. The estimated relative uncertainty of the device is about 200×10-6 in magnitude and less than 110 μrad in phase.
Published in:
Innovative Smart Grid Technologies (ISGT Europe), 2012 3rd IEEE PES International Conference and Exhibition on
Date of Conference: 14-17 Oct. 2012