An Improved Islanding Detection Method for a Grid-Connected Inverter With Intermittent Bilateral Reactive Power Variation

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

6 Author(s)
Jun Zhang ; Coll. of Electr. Eng., Zhejiang Univ., Hangzhou, China ; Dehong Xu ; Guoqiao Shen ; Ye Zhu
more authors

An islanding detection method for a grid-connected inverter incorporating intermittent bilateral (IB) reactive power variation (RPV) is described. The inverter output with IB reactive power enables the detection of an islanding. The RPV range is derived in order to eliminate the nondetection zone. The design scheme of variation time in the method is obtained by estimating the transient response due to islanding occurrence. In addition, the effect of the proposed detection strategy on power quality is investigated. The proposed islanding detection method has been experimentally verified on a three-phase grid-connected 6-kW inverter.