Application of six-sequence fault components in fault location for joint parallel transmission line

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
3 Author(s)
Fan, Chunju ; Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200030, China ; Cai, Huarong ; Yu, Weiyong

A new fault location method based on six-sequence fault components was developed for parallel lines based on the fault analysis of a joint parallel transmission line. In the six-sequence fault network, the ratio of the root-mean square value of the fault current from two terminals is the function of the line impedance, the system impedance, and the fault distance away from the buses. A fault location equation is given to relate these factors. For extremely long transmission lines, the distributed capacitance is divided by the fault point and allocated to the two terminals of the transmission line in a lumped parameter to eliminate the influence of the distributed capacitance on the location accuracy. There is no limit on fault type and synchronization of the sampling data. Simulation results show that the location accuracy is high with an average error about 2%, and it is not influenced by factors such as the load current, the operating mode of the power system, or the fault resistance.

Published in:

Tsinghua Science and Technology  (Volume:10 ,  Issue: 2 )