Movement of particles in compressed SF6 GIS with dielectric coated enclosure

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$33 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

3 Author(s)
K. S. Prakash ; British Columbia Univ., Vancouver, BC, Canada ; K. D. Srivastava ; M. M. Morcos

In compressed GIS (gas insulated switchgear), the control of wire particle contamination by dielectric coating of enclosure is demonstrated in this paper. Assuming that a particle acquires free charge through a partial discharge, the modeling of particle movement when the inside surface of a horizontal section of GIS/GITL (gas insulated transmission line) enclosure is coated is described. Under an applied 60 Hz ac voltage, the maximum height reached above the enclosure by a particle is much lower for a coated than for an uncoated enclosure. When the applied ac voltage varies, the maximum height reached depends on the magnitude of the applied voltage, phase and velocity at which the particle hits the enclosure. Typical results show that by coating the enclosure, the maximum height reached by a wire particle in a coaxial system can be reduced, thus inhibiting particle movement and minimizing the possibility of insulation breakdown

Published in: