Testing and performance of transformer differential relays

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

5 Author(s)
Stringer, N.T. ; Basler Electr. Co., Highland, IL, USA ; Lawhead, L. ; Wilkerson, T. ; Biggs, J.
more authors

The phenomenon of transformer magnetizing inrush current has been discussed in many papers throughout the years. A brief review of magnetizing inrush is given to provide the basis of need for transient testing. Previous studies have shown that inrush currents contain harmonic components of the fundamental waveform. Conventional philosophy has been to utilize the second harmonic current to provide inhibited operation of differential relays because of its dominance. Manufacturers have used various designs regarding higher order harmonics. The use of second and third, as well as the inclusion of all harmonics, have been seen over the years. The relay considered in this article utilized the second harmonic current to provide restraint on magnetizing inrush. The reasons for this are discussed. The authors discuss relay transient testing, EMTP transient testing, factory transient tests, EMTP testing facility, transformer differential EMTP tests, and EMTP transformer modeling. Several case studies relating to transformer differential relays are then discussed

Published in:

Industry Applications Magazine, IEEE  (Volume:3 ,  Issue: 4 )