This paper presents a new method for islanding detection of inverter-based distributed generation (DG). The main idea of this paper is to change the dc-link voltage considering the PCC voltage changes during islanding condition. A simple islanding detection scheme has been designed based on this idea. The proposed method has been studied under multiple-DG operation modes and the UL 1741 islanding tests. The simulations results, carried out by MATLAB/Simulink, show that the proposed method has a small nondetection zone. Also, this method is capable of detecting islanding accurately within the minimum standard time.
Published in:
Power Delivery, IEEE Transactions on
(Volume:26
,
Issue:
2
)
Date of Publication: April 2011