Analysis of transient dominant frequency signal for single-phase earthed fault based on prony algorithm

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Xin-hui Zhang ; Sch. of Electr. & Electron. Eng., Shandong Univ. of Technol., Zibo, China ; Shu-xian Fan ; Hao Duan ; Bing-yin Xu

The fact of a dominant resonance frequency existed in the transient process of short-circuit fault is discovered by analyzing transient characteristics of single-phase earthed fault. At this frequency, the amplitude of zero modal current in faulty feeder is much larger than that in healthy feeder, and their polarity is approximately opposite. Transient dominant frequency zero modal current in faulty feeder is 90deg lagged behind zero modal voltage of bus bar, while for healthy feeder it is 90deg leading zero modal voltage of bus bar. Vast simulations under diverse fault conditions have been done by using ATP program. The transient dominant frequency signal is extracted based on Prony algorithm and the corresponding fit data and wave-form is obtained, which completely proved the above conclusions.