Cart (Loading....) | Create Account
Close category search window
 

Resultant magnetic fields due to both windings and heavy current leads in large power transformers

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Tang Renyuan ; Shenyang Polytech. Univ., China ; Li Yan ; Lin Feng ; Tian Lijian

The eddy current field due to both windings and heavy current leads (HCL) in large power transformers is analyzed by using the improved T-Ω method, in which T and Ω can be solved separately in different subregions. Thus, storage capacity and CPU time can be saved to a great extent. In addition, the local overheating on the tank wall near the magnetic shield gap is calculated and analyzed, and improvement measures are proposed. On the basis of this work, a composite shield is analyzed and optimized. The numerical results show that the eddy current losses are reduced and the local overheating is removed by using this composite shield

Published in:

Magnetics, IEEE Transactions on  (Volume:32 ,  Issue: 3 )

Date of Publication:

May 1996

Need Help?


IEEE Advancing Technology for Humanity About IEEE Xplore | Contact | Help | Terms of Use | Nondiscrimination Policy | Site Map | Privacy & Opting Out of Cookies

A not-for-profit organization, IEEE is the world's largest professional association for the advancement of technology.
© Copyright 2014 IEEE - All rights reserved. Use of this web site signifies your agreement to the terms and conditions.