Investigation of transient induced voltage to a communication line from an overhead power transmission line

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $31
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

2 Author(s)
Imamura, T. ; Dept. of Electr. Eng., Doshisha Univ., Kyoto, Japan ; Ametani, A.

A transient voltage induced on a communication line by an overhead power transmission line is investigated using analytical formulas of the voltage and the maximum voltage value and on results calculated with EMTP and using a frequency-domain method. A large transient induced voltage, which is several times greater than the steady-state induced voltage during a line-to-ground fault, is generated because of the different propagation times of the aerial and earth-return modes in the case of a switching surge with no source inductance and that of a line-to-ground fault surge. The transient induced voltage in the switching surge case, with a source inductance, can be neglected because it is of the same order as the steady-state induced voltage during a fault. Based on a parametric analysis of the induced voltage, it was found that, the transient and steady-state induced voltages generally increase as the line length and earth resistivity increase, and as the source inductance and separation between the power and communication lines decrease

Published in:

Generation, Transmission and Distribution, IEE Proceedings C  (Volume:137 ,  Issue: 2 )