Analysis Results of Output Power Loss Due to the Grid Voltage Rise in Grid-Connected Photovoltaic Power Generation Systems

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

5 Author(s)
Ueda, Yuzuru ; Tokyo Univ. of Agric. & Technol., Tokyo ; Kurokawa, K. ; Tanabe, T. ; Kitamura, K.
more authors

This paper describes the connected photovoltaic (PV) power generation system's grid overvoltage protection function and summarizes the occurrence of the output power loss due to the grid voltage rise. Power injection from the PV system will raise the voltage at the power distribution line. A power conditioning subsystem (PCS) needs to regulate its output if the voltage becomes higher than the upper limit in order to avoid the overvoltage at the power grid. Thus, a PV system cannot generate electricity under the high grid voltage. There are 553 residential PV systems installed in Ota, Japan, for the demonstration research project of clustered PV systems. Measurement data of these 2.1-MW grid-connected PV systems are used for the analysis. Only the limited number of PV systems experienced a significant amount of output energy loss due to the high grid voltage in a particular day, whereas the other system's outputs also raise the grid voltage. The causes of this maldistribution of the output energy loss are the difference of the line impedance, the difference of the starting voltage of the PCS's grid overvoltage protection function, and the imbalance of the load in single-phase three-wire power distribution systems. The present control of the PCS successfully avoids the overvoltage on the grid but cannot share the loss.

Published in:

Industrial Electronics, IEEE Transactions on  (Volume:55 ,  Issue: 7 )