Investigations of Temperature Effects on the Dielectric Response Measurements of Transformer Oil-Paper Insulation System

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

2 Author(s)
Saha, T.K. ; Queensland Univ., Brisbane ; Purkait, P.

Dielectric testing techniques, in both time and frequency domains, are currently widely used by power utilities for assessment of the condition of transformer oil-paper insulation systems. However, it has been reported that results of these tests are highly influenced by the operating temperature during measurements. The distribution, migration and equilibrium of moisture between oil and paper in a complicated insulation system is highly temperature dependent. It requires adequate experience and proper understanding to interpret the dielectric response results in the presence of temperature variations and thermal instability. Proper analysis of the dielectric test result is only possible with an understanding of the physical behavior of the insulation system in response to temperature. A circuit model, which describes the dielectric behavior of the transformers main insulation system, has been investigated in this paper. The values of the parameters of the model have been identified from the dielectric tests. A correlation has been observed between the operating temperature and the equivalent model parameters that can be used as additional information for better interpretation of the dielectric test results. This paper thus reports a detailed study on the effects of temperature on dielectric measurements of a transformer under controlled laboratory conditions. Some results of practical on-site testing are also presented to demonstrate the possibility of errors that may be introduced in dielectric test results analysis unless temperature effects are taken into consideration.

Published in:

Power Delivery, IEEE Transactions on  (Volume:23 ,  Issue: 1 )