Loss-of-Excitation Protection for Synchronous Generators on Isolated Systems

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

1 Author(s)
Pierre, Conrad R.St. ; General Electric Company, ISPEO, Building 6-303, 1 River Road, Schenectady, NY 12345.

Loss-of-field relays operating on an impedance-measuring principle provide an important part of the protection of a synchronous generator by minimizing possible damage to the machine and low voltages detrimental to system operation. These relays require an external source of reactive power, such as a utility tie or other in-plant generators, to insure proper operation on loss of generator field. In a multigenerator isolated system, the reactive current provided by the remaining generators may not be sufficiently large to allow proper operation of the loss-of-field relays on the generator in question. Some guidelines are provided as to the relative size of synchronous generators needed to insure proper operation of the impedance type loss-of-field relays.

Published in:

Industry Applications, IEEE Transactions on  (Volume:IA-21 ,  Issue: 1 )