2 Author(s)

Extensive analysis and testing with real time data of the AEP system for various types of equivalencing techniques has been performed. It was found that for real time on-line applications the REI-type equivalents performed better than other equivalencing methods (Ward-type equivalents). It is shown that the equivalent updating procedure used for REI-type equivalents cannot be used for Ward-type equivalents. Ward-type equivalents which performed well for off-line planning applications and for some simulated real time applications did not work as well under realistic on-line conditions.

Published in:

Power Apparatus and Systems, IEEE Transactions on  (Volume:PAS-100 ,  Issue: 12 )