The feasibility of a qualitative approach for detecting faults in an air-conditioning system is considered. The system considered is a multi-zone variable air volume air-handling unit, and the faults investigated include types which result in deterioration of operation, as distinct from actual failure. The operating modes of the sequential controller for the central air-handling plant can be matched to a corresponding qualitative classification of steady-state temperatures. Observed mismatches indicate the presence of faults. Trials of the method in an air-conditioning test laboratory are reported

Published in:
Control Systems, IEEE  (Volume:15 ,  Issue: 4 )

Date of Publication: Aug 1995

Need Help?


IEEE Advancing Technology for Humanity About IEEE Xplore | Contact | Help | Terms of Use | Nondiscrimination Policy | Site Map | Privacy & Opting Out of Cookies

A not-for-profit organization, IEEE is the world's largest professional association for the advancement of technology.
© Copyright 2013 IEEE - All rights reserved. Use of this web site signifies your agreement to the terms and conditions.