This paper presents a simplified high-frequency model for three-phase, twoand three-winding transformers. The model is based on the classical 60 Hz equivalent circuit, extended to high frequencies by the addition of the winding capacitances and the synthesis of the frequency-dependent short-circuit branch by an RLC equivalent network. By retaining the T-form of the classical model, it is possible to separate the frequency-dependent series branch from the constant-valued shunt capacitances. Since the short-circuit branch can be synthesized by a minimum-phase-shift rational approximation, the mathematical complications of fitting mutual impedance or admittance functions are avoided and the model is guaranteed to be numerically absolutely stable. Experimental tests were performed on actual power transformers to determine the parameters of the model. EMTP simulation results are also presented
Published in:
Power Delivery, IEEE Transactions on
(Volume:10
,
Issue:
3
)
Date of Publication: Jul 1995