Study on eddy current losses and shielding measures in large power transformers

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Chen Yongbin ; Shenyang Transformer Res. Inst., China ; Yang Junyou ; Yu Hainian ; Tang Renyuan

The improved T-Ω method is applied to the computation of the three dimensional eddy current field in a 360 MVA/500 kV large power transformer, the structure of which is complicated. The different cases of tank wall with magnetic shunt, aluminium screen or without any shield are analyzed. The relations between eddy current losses and the materials, structure and size of the tank shield are presented. Compared with a parallel magnetic shunt arrangement, the vertical magnetic shunt reduces stray losses by 63.8%. The optimal thickness of the vertical magnetic shunt is 10 mm. The magnetic shunt should be spread over 0.5 mm at both ends of windings in the 360 MVA/500 kV large power transformer

Published in:

Magnetics, IEEE Transactions on  (Volume:30 ,  Issue: 5 )