Measurement of harmonic currents and evaluation of the DC filter performance of the New England-Hydro-Quebec Phase I HVDC project

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Garrity, T.F. ; Ebasco Services Inc., New York, NY, USA ; Hassan, I.D. ; Adamson, K.A. ; Donahue, J.A.

Measurements were conducted to determine the cause of increased telephone interference and to evaluate the DC filter performance. The measurements revealed unexpected high levels of three-pulse harmonic currents in the DC pole conductors. The cause is attributed to imbalances within the six-pulse bridges caused by the converter transformer and valve stray capacitances to ground. The conventional model of the converter power circuit used as the basis for the DC filter design does not reproduce the measured three-pulse harmonics