Cart (Loading....) | Create Account
Close category search window
 

Note on the Measurement of Transformer Turns-Ratio

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

1 Author(s)
Honnell, P.M. ; Signal Corps, U.S. Military Academy, West Point, New York

This note shows that in many important cases the turns-ratio of iron-core transformers is given by the simple relation N1/N2= √Xsc1/Xsc2, in which Xsc1and Xsc2are the reactive components of the short-circuit primary and secondary impedance of the windings concerned. The measurements are conveniently made with an impedance or inductance bridge. This equation also gives the turns-ratio of certain air-core transformers.

Published in:

Proceedings of the IRE  (Volume:33 ,  Issue: 11 )

Date of Publication:

Nov. 1945

Need Help?


IEEE Advancing Technology for Humanity About IEEE Xplore | Contact | Help | Terms of Use | Nondiscrimination Policy | Site Map | Privacy & Opting Out of Cookies

A not-for-profit organization, IEEE is the world's largest professional association for the advancement of technology.
© Copyright 2014 IEEE - All rights reserved. Use of this web site signifies your agreement to the terms and conditions.