This note shows that in many important cases the turns-ratio of iron-core transformers is given by the simple relation N1/N2= √Xsc1/Xsc2, in which Xsc1and Xsc2are the reactive components of the short-circuit primary and secondary impedance of the windings concerned. The measurements are conveniently made with an impedance or inductance bridge. This equation also gives the turns-ratio of certain air-core transformers.