3 Author(s)
Xu Yan ; Key Lab. of Power Syst. Protection & Dynamic Security Monitoring & Control, North China Electr. Power Univ., Baoding ; Liu Qing ; Wang Zengping

This paper presents a new scheme for transformer differential protection based on the OCT. The scheme can operate reliably when internal faults occurred and do not operate in the condition of external faults, inrush and overexcitation. This scheme combines harmonic restraint and blocking methods with dc content blocking. In this paper, the digital signal processor (DSP) is applied to improve computation and render fast protection feasible. The novel transformer protection system interface construction, hardware structure, software algorithm are discussed. Performance analysis shows its has distinguish advantages over the traditional transformer protection

Published in:

Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES

Date of Conference:

21-24 May 2006