Accelerated trip scheme for second-zone distance protection

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$33 $33
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

3 Author(s)
T. S. Sidhu ; Univ. of Western Ontario, Ont., Canada ; P. Ye ; M. S. Sachdev

The theoretical aspects, design and testing of a new accelerated trip scheme for second-zone distance protection of HV/EHV transmission lines is described. The scheme is simple and provides relatively high-speed (60-70 ms) operation of the second-zone distance protection without requiring a communication channel. The scheme has been extensively tested using EMTDC simulations under various power system operating conditions. Simulation results show that the selectivity and speed of the proposed scheme are satisfactory for practical use in HV/EHV transmission line distance relays.

Published in:

IEE Proceedings - Generation, Transmission and Distribution  (Volume:150 ,  Issue: 3 )