Analysis of operating conditions of ground-fault protection schemes for generator stator winding

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

2 Author(s)
Zielichowski, M. ; Inst. of Electr. Power Eng., Wroclaw Univ. of Technol., Poland ; Fulczyk, M.

This paper presents results of simulation studies of the influence of methods of grounding the stator winding of the unit-connected generator neutral on the operating conditions of a 100-percent ground-fault protection excited by the third-harmonic voltage ratio in the generator neutral and at its terminals. The analysis was performed for a generator with the neutral grounded through a ground-fault neutralizer, a third-harmonic stop filter, a resistor, and a capacitive voltage divider. The influence of the parameters of the particular elements of the grounding circuits on the voltage-feeding measuring element of the protection was determined. The capacitance to ground of the generator breakers was taken into account. The simulations were run for 1110-MVA unit-connected generator at ground faults along the whole length of the generator stator winding. It has been found that the method of grounding the generator neutral and the parameter of the grounding elements significantly influences the operating conditions of this protection. It is shown that through the proper selection of these parameters, the ground-fault protection of whole stator winding, counting from the generator neutral to the terminals is ensured.

Published in:

Energy Conversion, IEEE Transactions on  (Volume:18 ,  Issue: 1 )