Experimental facility for investigation of lightning performance of distribution lines

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

3 Author(s)
Nakada, K. ; Central Res. Inst. of Electr. Power Ind., Hokuriku Electr. Power Co., Tokyo, Japan ; Sugimoto, H. ; Yokoyama, S.

In order to clarify the lightning performance of a distribution line, test distribution lines and a test tower were constructed at the Mikuni Testing Center of Hokuriku Electric Power Company in 1999. Using these facilities, the authors observed transient voltages and current distributions due to direct strokes of natural lightning. Based on this data, we have clarified the following points: (1) calculated voltages and currents using the EMTP agree with the experimental results fairly well; and (2) for lightning currents of long durations, however, the reduction of voltages across arresters by energy absorption should be taken into consideration.

Published in:

Power Delivery, IEEE Transactions on  (Volume:18 ,  Issue: 1 )