High-frequency characterization and modeling of distribution transformers

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

The purchase and pricing options are temporarily unavailable. Please try again later.
2 Author(s)
Black, W.C. ; Northern Microdesign, Inc., Ames, IA, USA ; Badr, N.E.

Distribution transformers are generally assumed to block high frequency power line carrier signals and to require bypass networks where signals must cross a transformer. In this work, however, we show experimentally that significant coupling occurs at some frequencies both across distribution transformers and between different transformer phases in various commercial transformers. This suggests that the transformers may pass noise and coupled RF signals between low and medium voltage power lines much more readily than predicted by simple models. It also suggests that frequency adaptive or spread-spectrum methods should be able to communicate across distribution transformers without bypass networks. Measured results are applied to a commercial simulator model suitable for use within large simulations.

Published in:

Power Line Communications and Its Applications (ISPLC), 2010 IEEE International Symposium on

Date of Conference:

28-31 March 2010