This paper presents alternative approaches using artificial neural networks (ANNs) for the protection of power transformers. A complete protection scheme was implemented. An ANN subroutine was used to discriminate internal faults from other situations, replacing the traditional Fourier method for harmonic restraint. In addition, a routine for reconstruction of saturated current signals based on recurrent ANNs is also proposed. The proposed methods were extensively tested and then compared to the traditional differential protection algorithm, showing promising results. The application of the ANN tools is a new and important stage in the differential relay analysis methodology for power transformer protection
Published in:
Power Systems, IEEE Transactions on
(Volume:21
,
Issue:
3
)
Date of Publication: Aug. 2006