Partial-discharge-inception testing on low-voltage motors

Sign In

Cookies must be enabled to login.After enabling cookies , please use refresh or reload or ctrl+f5 on the browser for the login options.

Formats Non-Member Member
$31 $13
Learn how you can qualify for the best price for this item!
Become an IEEE Member or Subscribe to
IEEE Xplore for exclusive pricing!
close button

puzzle piece

IEEE membership options for an individual and IEEE Xplore subscriptions for an organization offer the most affordable access to essential journal articles, conference papers, standards, eBooks, and eLearning courses.

Learn more about:

IEEE membership

IEEE Xplore subscriptions

4 Author(s)
Bogh, D. ; Gen. Electr.-Motors, Woodinville, WA, USA ; Coffee, J. ; Stone, G. ; Custodio, J.

This is a review of one manufacturer's efforts toward testing National Electrical Manufacturers Association (NEMA) low-voltage motor insulation for compatibility with adjustable-speed drives (ASDs). Partial-discharge-inception-voltage (PDIV) measurements were selected as a tool to evaluate the future performance of the stator insulation system to resist deterioration by the drives. PDIV measurement is explained in terms of procedure and accuracy. Data are presented from tests made on motors from several prominent manufacturers.

Published in:

Industry Applications, IEEE Transactions on  (Volume:42 ,  Issue: 1 )