Abstract:
This paper derives a set of sufficient conditions guaranteeing that the load-flow problem in unbalanced three-phase distribution networks with wye and delta constant-powe...Show MoreMetadata
Abstract:
This paper derives a set of sufficient conditions guaranteeing that the load-flow problem in unbalanced three-phase distribution networks with wye and delta constant-power, constant-current, and constant-impedance loads (ZIP loads) has a unique solution over a region that can be explicitly calculated from the network parameters. It is also proved that the well-known Z-Bus iterative method is a contraction over the defined region, and hence converges to the unique solution.
Published in: IEEE Transactions on Power Systems ( Volume: 33, Issue: 1, January 2018)