Abstract:
We use synchrophasor measurements of the complex voltage and current at both ends of multiple transmission lines that connect areas of a power system to monitor the onlin...Show MoreNotes: This article was mistakenly omitted from the original submission to IEEE Xplore. It is now included as part of the conference record.
Metadata
Abstract:
We use synchrophasor measurements of the complex voltage and current at both ends of multiple transmission lines that connect areas of a power system to monitor the online voltage collapse margin. A new reduction is used to reduce the multiple transmission lines to a single line equivalent and determine how to combine the synchrophasor measurements. Generator reactive power limits can be accommodated. The results show that this methodology can capture the effect of multiple contingencies inside the transmission corridors, giving awareness to the operators about the severity of contingencies with respect to voltage stability.
Notes: This article was mistakenly omitted from the original submission to IEEE Xplore. It is now included as part of the conference record.
Published in: 2015 IEEE Power & Energy Society General Meeting
Date of Conference: 26-30 July 2015
Date Added to IEEE Xplore: 04 February 2016
Electronic ISBN:978-1-4673-8040-9
Print ISSN: 1932-5517